Secured Trading Service

New Type Multi Funcation Circuit Breaker RCBO

Wenzhou Santuo Electrical Co., Ltd.
  • Audited Supplier
  • 10 yrs

Contact Supplier

Still deciding? Get samples of $ !
Request Sample

Product Highlights

  • Multi-Function Protection: Integrates overcurrent, leakage, over/under voltage, and overtemperature protection in one device.
  • Adjustable Parameters: Rated current (10-100A), leakage current (30-300mA), and voltage thresholds are fully adjustable.
  • High Breaking Capacity: Rated short-circuit capacity of 6000A ensures reliable performance in industrial and commercial systems.
  • Real-Time Monitoring: Features real-time query for voltage, current, leakage, and temperature with LED indicators.
  • Safety Alarms: Emits audible alarms for phase loss, PE line disconnection, or water immersion to prevent accidents.
  • CE & ISO Certified: Complies with IEC61009-1 and GB16917.1 standards, holding CE, ISO9001, CB, and SAA certifications.
  • DIN Rail Mounting: Compact structure designed for easy installation on standard 35mm DIN rails.
  • Long Service Life: Mechanical life of 10,000 operations and electrical life of 4,000 operations for durability.

Shipping

Shipping Cost:
Contact the supplier about freight and estimated delivery time.

Online Trading Protection

Payment Guarantee
T/T PayPal ApplePay GooglePay visa mastercard american express discover JCB diners club PIX SPEI OXXO PSE OZOW Platform-protected payments with refund support for eligible order issues.
Platform Logistics
Clearer shipment tracking with platform-supported logistics.
Inspection Service
Optional pre-shipment inspection for quality and quantity checks.
After-Sales & Dispute Handling
Platform-assisted dispute resolution, including refunds or returns when applicable.

Only orders placed and paid through Made-in-China.com Secured Trading are eligible for payment protection and the corresponding platform services.

Product Images of New Type Multi Funcation Circuit Breaker RCBO

New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO pictures & photos
New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO pictures & photos
New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO pictures & photos
New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO pictures & photos
New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO pictures & photos
New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO pictures & photos
New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
    New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
    New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
    New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
    New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
    New Type Multi Funcation Circuit Breaker RCBO
  • New Type Multi Funcation Circuit Breaker RCBO
    New Type Multi Funcation Circuit Breaker RCBO

Find Similar Products

Product Description

Product Description

GENERAL
STSF2-100 series Multi function residual current circuit breaker with over current protection(RCBO)is suitable for AC 50/60Hz,
rated
 in a circuit with a voltage of 230V-400V and a rated current of 100A,when a person is electrocuted or the power grid leaks..

When the leakage,overvoltage,and undervoltage reach the set values,the residual current circuit breaker can quickly operate  in a very short period of time quickly cut of the power supply.When the monitoring temperature of the residual current circuit breaker reaches the set value,the monitoring ground wire is not connected.

When connected,the product emits an alarm sound to protect the safety of personnel and electrical equipment,
and
 can avoid 
Prevent damage to equipment caused by overvoltage in the power grid.It has overload,short circuit,leakage,
overvoltage, u
ndervoltage and overtemperature protection functions can also be used to intermittently turn on and off electrical
 devices under normal circumstances l
ighting circuits,especially suitable for industrial and commercial lighting distribution systems.

The product has a small volume,compact structure,and better cost effectiveness than other similar products.It has a beautiful 
appearance,h
igh breaking capacity makesit a good choice for household power distribution.This product complies with
GB/T
 16917.1 and IEC61009-1 standards and has obtained CE certification.


SURROUNDING    AIR     TEMPERATURE:
1.The ambient air temperature shall not be lower than -5ºC,not higher than+40ºC,and the daily average value shall 
not exceed +35ºC .


2.Altitude:The altitude of the installation site shall not exceed 2000m.

3.Atmospheric conditions
The air is clean,and at a maximum temperature of+40ºC,the relative humidity of the air is not high More than 50%.Higher relative humidity is allowed at lower temperatures,such as at+20ºC,
The relative humidity should not exceed 90%.Due to occasional moderate condensation caused by temperature changes,
attention should be paid to taking appropriate measures.


4.Installation  Category :DIN RAIL Installation.

  
5. Recommended selection principles:
5.1 General selection principles
a)The rated working voltage of RCBO ≥ the rated voltage of the line.
b) The rated current of RCBO is 1.1-1.25 times the load current calculated by the line.
c)The rated short-circuit breaking capacity of RCBO ≥ the maximum short-circuit
current that may appear in the line.
d)RCBO instantaneous release setting current ≤ 0.8 times the end of the line phase
-to-ground or phase-to-phase short circuit current.
e) Single-phase rated current of electric heaters, refrigerators and incandescent la-
mps at a given voltage and power In=P/U; three-phase rated current In=P/1.732U.
RCBO residual current is generally selected as 30mA, which is used as personal
contact protection.
To install and use the product, please read the retention manual.

New Type Multi Funcation Circuit Breaker RCBO
New Type Multi Funcation Circuit Breaker RCBO

New Type Multi Funcation Circuit Breaker RCBO

User's Guide and Function:

Operation Guide for the Multi-Function Residual Current Circuit Breaker (RCBO):
1.Press the SET button to enter the settings interface;
2. OV----Over/Under Voltage (230V-300V) Adjustable: Adjust with up and down keys (V);
3. The interface displays 05-5 (05 indicates the delayed trip time in seconds; 5 denotes a 5% time error);
4. UV---Under Voltage (160V-210V) adjustable; adjust with up/down keys (V); this product also features phase loss protection; if UV occurs on the 3P+N+PE three-phase product, it may be due to phase loss protection; product trips;
5. The interface displays 05-5 (05 indicates the delayed trip time (seconds); 5 represents a 5% time error;
6. OC----Rated current; 63 type (10-63A) adjustable; 100 type (10-100A) adjustable; Adjust with up and down keys (setting);
7. RCD---Leakage Current (30-300mA) Adjustable; Adjust via Up/Down Keys (Setting)
8. The interface displays 05-5 (05 indicates the delayed trip time in seconds; 5 represents a 5% time error;
9. OH---Temperature Protection Parameter (Adjustable between 60-120°C, use up/down keys to set);
10. Leakage current shut-off function: Press and hold the OK button for 3 seconds until the screen turns off. Release the button, and the RCD indicator will flash, indicating the leakage current function is disabled. To restore the leakage current function, press and hold the OK button for 3 seconds until the screen turns off. Release the button, and the RCD indicator will stop flashing, confirming the leakage current function is operational. ```Directly output the translation without explanation, ensuring the semantics are smooth.```
11. After completing the above function settings, press the OK button to save the parameter settings.
12. If the line is submerged in water, the product will emit a beeping alarm but will not trip (the product must be connected to the output PE line);
13. When the PE line input is invalid or not connected, the GFCI indicator on the product screen flashes, the grounding indicator light turns off, the product emits a buzzer alarm, and the product trips for protection.
14. Real-time parameter query function: Press the button to sequentially check the real-time voltage value, phase A, B, and C current values, leakage current value, and temperature value.
15. Notes: The product must strictly adhere to the wiring as indicated on the product. L -- live wire; Line -- input wire; N -- neutral wire; PE -- ground wire
16. 1).This product must be operated by a professional electrician (holding an electrician certificate).
   2).All responsibility for safety accidents during installation by non electricians shall be borne by the user.



Warn!

1. This product must be wired and installed by qualified personnel;
2. It is strictly forbidden to operate the leakage circuit breaker with wet hands,
otherwise electric shock accidents may occur;
3. Leakage circuit breakers cannot be used for personal electric shock caused by
simultaneous contact with the two lines of the protected circuit. Protect;
4. When the leakage circuit breaker is used for the action characteristic test, it
should be tested and qualified by the relevant state departments. It is strictly
forbidden to use the test method of directly touching the grounding device or direct
short circuit;
5. It is strictly forbidden to directly test the insulation resistance at the outlet of the
product; the power supply of the electronic circuit board should be disconnected,
And ensure that there is no voltage at the input and output terminals of electronic
components before testing, otherwise the circuit board will be burned electronic co-
mponents;
6. The overload, short circuit and residual current protection characteristics of the
leakage circuit breaker are all set by the manufacturer. It is allowed to disassemble
and adjust at will;
7. After the leakage circuit breaker is opened due to the failure of the protected circuit
(leakage, overload or short circuit, etc.), The reason must be
found out, and the closing operation can only be performed after troubleshooting:
8. It is strictly forbidden to connect the load when the leakage circuit breaker is closed:
9. During use, there should be no phase failure or "N" wire disconnection on the power
supply side. Wiring, this product cannot play the role of leakage protection.
Precautions!
1. Leakage circuit breakers must not be attacked by rain or snow during transportation,
storage and use.
2. Before installation, check whether the basic technical data of the signs and signs
meet the requirements (the selected current The size should match the actual use):
manual operation several times should be flexible, confirm that it is intact, Installation:
When installing, wires that can withstand the corresponding current carrying capacity
should be selected. See attached table 3 for reference values.
3. Strictly follow the wiring diagram for installation.
4. Run check: 4.1 Check whether the wiring is correct, especially check that the
input terminal of the leakage circuit breaker should be connected to the power supply,
and the output terminal should be connected to the load.
4.2 Confirm that the screws of each terminal have pressed the wire tightly, and the  wire
should be in the corresponding wiring frame.
4.3 Close the leakage circuit breaker and press the test button to check whether the
leakage protection performance is normal and reliable. If the leakage circuit
breaker can be disconnected normally, the indicator will be red.
5. After the leakage circuit breaker has been running for a certain period of time
(usually one month), it is necessary to press the test button in the closed and energ-
ized state to check whether the leakage protection performance is normal andreli-
able (press the test button once a month, and the leakage circuit breaker should be
broken once). In case of failure, it should be removed and sent to the manufacturer
for repair.
6. The neutral wire () at the outlet end can only be used as a working neutral wire, not
a protective neutral wire. 7. When the leakage exitable model is selected, the leakage
"exit" function of the circuit breaker is an emergency use function, which is only used
by professional power supply maintenance personnel in emergency maintenance situations.
After maintenance, it must be put into leakage protection function status immediately.


Product Over View and Function:

1.Multi Function: New Type Multi Funcation Circuit Breaker RCBO

2.High short-circuit current withstand capacity

3.Applicable to terminal and pin/fork type busbar connection

4. Equipped with finger protected connection terminals

5.Automatically disconnect the circuit when earth fault/leakage current occurs and exceeds the rated sensitivity6.Independent of power supply and line voltage, and free from external interference, voltage fluctuation.
New Type Multi Funcation Circuit Breaker RCBO

SPECIFICATIONS
  Standard  Unit IEC/EN 61009-1

Electrical

features

Mode    Electronic type
Type(wave form of the earth leakage sensed)    AC
Thermo-magnetic release characteristic   B,C,D
Rated current ln A 6-100A(6,10,16,20,25,32,40,63;80,100A)Adjustable
Poles P 1P+N+PE, 3P+N+PE
Rated voltage Ue V AC 230, 400  (Adjustable)
Rated sensitivity I△n A 30-300mA(30,100,300mA) Adjustable
Rated residual making and breaking capacity l△m A 500
Rated short-circuit capacity Icn A 6000
Break time under I△n S ≤0.1
Rated frequency Hz 50/60
Rated impulsewithstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind.Freq for 1min kV 2
Insulation voltage Ui V 250
Pollution degree   2
Other function Over/under voltage protection;  and  Temperature protection  ; Fire-alwarm and others

Mechanical

features

Electrical life   4000
Mechanical life   10000
Fault current Indicator   YES

Protection degree

 

IP20

Ambient temperature

(with daily average≤35ºC)

ºC

-5~+40(Special application please refer to

temperature compensation correction)

Storage temperature ºC -25~+70
Installation Terminal connection type   Cable/Pin-type busbar/U-type busbar
     
Terminal size top/bottom for cable mm2 25
AWG 18-5
Terminal size top/bottom for busbar mm2 25
AWG 18-3
Mounting   On DIN rail EN 60715(35mm)by means of fast clip device
Connection   From top


New Type Multi Funcation Circuit Breaker RCBO
Our Services:

  1. Competitive price
  2. Continuance Service and support
  3. Good-after service
  4. Quality Reliability and Long Product Life.

New Type Multi Funcation Circuit Breaker RCBO

FAQ

Q1. What advantages do you have?

A1. We are the direct Manufacturer in Wenzhou China , we have professional,our teams have more than 20years experience in the field.
developing, marketing & production team to offer you the most competitive price and best service.

Q2. What's your main product?
A2. Circuit Breaker(MCB,RCCB/RCD, RCBO,ELCB, MCCB, ACB); Ac Contactor, Thermal Relay, Magnetic Starter; Isolator Switch, Changeover Switch, Push Button Switch, Voltage Protector...

Q3. Could you print our own logo?
A3. Yes, Our company are available for Retail & Wholesale & OEM & ODM.

Q4. How long is the quality guarantee?
A4. 18 month warranty, our products are 100% inspection.

Q5. How long is the deliver time?
A5. It usually takes about 3 - 5 working days for sample order and 10 - 25 days for big order.

Q6. What is your payment terms?
A6. Our Payment term is T/T,  PayPal,  L/C at sight.

Q7. Any certification of your company or product?
A7.We have ISO 9001, CE, CB, SAA.

 

About the Supplier

Watch Video
Watch Video
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.
Wenzhou Santuo Electrical Co., Ltd.

About Our Factory & Business Background

Address
No. 3999 Liujiang Road, Liushi Yueqing, Wenzhou, China.
Terms of Payment
LC, T/T, D/P, PayPal
International Commercial Terms(Incoterms)
FOB, EXW, CFR, CIF
Average Lead Time
Peak Season Lead Time: 1-3 months
Off Season Lead Time: within 15 workdays
Nearest Port
NINGBO

Our Production Capability & Technical Expertise

Main Products
Circuit Breaker, AC Contactor, Thermal Relay, Magnetic Starter, Switch, Industrial Plug, Motor and Mechnism of Acb, Power Distribution Case, Voltage Regulator, Push Button Switch

Our Industry Experience & Global Business Record

Export Year
2016-01-08
Main Markets
South America, Eastern Europe, Southeast Asia, Africa, Mid East, Eastern Asia, Western Europe

FAQ

What protections does this RCBO offer?
It provides overload, short circuit, leakage, overvoltage, undervoltage, and overtemperature protection.
Is the rated current adjustable?
Yes, the rated current is adjustable: 10-63A for the 63 type and 10-100A for the 100 type.
What certifications does the product have?
The product holds CE, ISO9001, CB, and SAA certifications and complies with IEC61009-1 standards.
What is the warranty period?
We provide an 18-month warranty, and all products undergo 100% inspection before shipment.
Can we print our own logo?
Yes, we support OEM and ODM services, including custom logo printing for retail and wholesale.
What are the delivery times?
Sample orders take 3-5 working days, while bulk orders take 10-25 days depending on quantity.
What payment terms do you accept?
We accept T/T, PayPal, and L/C at sight for payment.
What is the breaking capacity?
The rated short-circuit breaking capacity is 6000A, suitable for high-demand industrial applications.

Send your message to this supplier

Contact Information
Recipient
Message

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now